Skip to main content

KE-IU3111-ZME

Excellence series intelligent addressable zone monitoring unit with isolator (ext. power)
  • Externally powered, allowing for the maximum number of devices to be installed on the loop
  • Provides an addressable, convectional zone for standard or intrinsic safe applications
  • Provides full zone supervision for standard, EN54-13 and BS5839 zone operation
  • Supports CleanMe™ for reporting maintenance alerts from conventional detectors
  • Supports detector only, MCP only and mixed zones
View all

At a glance

General

The innovative Excellence series of intelligent addressable devices offers advanced features for reliability and peace of mind. Coupled with features for ease of installation and maintenance on new fire detection systems, it’s a perfect match for exceptional overall performance.
The Excellence series input/output devices are designed to provide much needed flexibility to input monitoring and output switching. These modules, combined with the powerful features of a Kidde Excellence series addressable CIE, give customers versatility for diverse applications.
The KE-IU3111-ZME is an Excellence series addressable 2-wire zone monitor with integrated short circuit loop isolation. It offers an interface between conventional fire devices and an Excellence series addressable CIE, and enables the CIE to monitor the operation of up to 32 conventional devices in standard, or up to 20 detectors in intrinsically safe configurations.

Applications

The KE-IO3111-ZME is designed to allow the inclusion of any conventional fire zone into an Excellence addressable loop. With selectable support for multiple operating modes, it offers unmatched flexibility. Supported modes include:
Regulatory
* EN54-13 and BS5839 (head-out)
Special applications
* CleanMe™ (maintenance), Intrinsic safe
Standard
* Detector, manual call point or mixed zones
The KE-IU3111-ZME may be located anywhere on the Kidde Excellence loop where it occupies only 1 of 128 available addresses. Housed in a low profile molding, the interface is designed to clip directly onto a standard DIN rail fixing or be installed in a suitable wall mount housing.

Installation & Maintenance Features

The KE-IU3111-ZME is connected to the CIE via a 2-wire communication loop that carries the control data. Tri-Colour LED indicators positioned on the front face of the unit provide the engineer with clear identification of the operational state of the unit, as well as the status of any input and/or output control. Additional manual test facilities on the unit allows local testing without the need for control panel intervention, saving time during installation and commissioning.
Excellence series devices use an advanced digital data communications protocol with extensive error correction algorithms to ensure system reliability.

Details

  • Externally powered, allowing for the maximum number of devices to be installed on the loop
  • Provides an addressable, convectional zone for standard or intrinsic safe applications
  • Provides full zone supervision for standard, EN54-13 and BS5839 zone operation
  • Supports CleanMe™ for reporting maintenance alerts from conventional detectors
  • Supports detector only, MCP only and mixed zones
  • Supports DIN or wall mounting for installation flexibility
  • Local, clear operation status indication for ease of maintenance
  • Local test features for ease of validation

Technical specifications

General
Status indication
Tri-coloured LEDs
Compatibility
Kidde Commercial Excellence Systems
Addressing method
DIP Switches
Address range
1 to 128
Electrical
Power supply type
24 VDC
Operating voltage
17 to 29 VDC (loop)
22 to 28 VDC (external)
Current consumption
From the loop: 250 µA @ 24 VDC (standby), 2.5 mA @ 24 VDC (alarm)
From the external supply: 12 mA @ 24 VDC (standby), 32 mA @ 24 VDC (alarm)
Communication voltage
4 to 11 V (pulsed)
Cable specification PSU: 0.5 to 4.9 mm² shielded/unshielded twisted-pair
Input
Input quantity
1
Input type and rating
Supervised zone, <35 mA
Input states
Active
Fault
Normal
Open
Short
Supervisory voltage
14.3 to 23 VDC (application specific)
Alarm resistor
100 Ω ±5% (MCP) / 160 to 470 Ω ±5% (Detector)
Termination resistor
Application specific
Cable specification Zone: 0.5 to 4.9 mm² shielded/unshielded twisted-pair, < 2 km
Output
Output quantity
1
Output type and rating
NO/COM/NC relay, 2 A @ 30 VDC (resistive load)
Cable specification Relay: 0.13 to 3.31 mm² shielded/unshielded twisted-pair
Isolation
Type
Negative line break
Loop current
2.5 mA (active)
Series resistance
<0.08 Ω
Switch current
1.05 A (continuous) / 1.4 A (short)
Leakage current
<1 mA
Isolation voltage
14 to 15.5 VDC
Reconnect voltage
14 to 15.5 VDC
Impedance requirements ≤ 32 devices between isolators
Quantity per loop 128
Physical
Physical dimensions
148 x 102 x 27 mm
Net weight
145 g
Colour
Signal white (RAL 9003)
Mounting type
DIN-rail
Surface mount
Wall mount
Material
PC / ABS
Cable specification
Loop: 0.13 to 3.31 mm² shielded/unshielded twisted-pair (< 52 Ω / 500 nF)
Environmental
Vandal proof
No
Operating temperature
-22 to +55°C
Storage temperature
-30 to +65°C
Relative humidity
10 to 93% noncondensing
Environment
Indoor
Outdoor
IP rating
IP30 (without enclosure)
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-13, EN54-17, EN54-18

Compatible products

Category Reference Description
Enclosures N-IO-MBX-1 DIN Rail Module Box
Enclosures N-IO-MBX-2 DIN Rail Module Box
Interface unit N-IO-SBX-2G Single module box with DIN rail (large)