Skip to main content

KE-AS3111W

Excellence Series intelligent addressable sounder/visual indicator w/ isolator
  • Standard first fix base shared with point detectors for ease of planning, logistics and installation
  • Integrated short circuit loop isolation for added safety protection
  • Base lock, address tag, trim skirt and surface cabling support for easy installation in all conditions
  • Loop powered with battery assisted activation allowing up to 128 devices per loop
  • 32 selectable tones at 4 selectable volume levels that can be reconfigured from the CIE
View all

At a glance

General

The AS2366W is a WHITE bodied, shallow base addressable room sounder/beacon for fire alarm systems running 2000 series addressable fire protocol. Multiple tone selection and full CPD approval ensure conformance to local regulations. The beacon has a RED lens and a flash frequency of 1 Hz.

The sounder/beacons operate over a 2-wire 2000 series loop and are loop powered i.e. no external power supply is required. They are compatible with automatic phased-start synchronisation controlled from the fire panel.

Installation

Device cabling is done to the base and allows the sounder to be fitted and locked into position afterwards. A separate earth terminal is provided in the base for connecting the screen or functional earth when required.

Efficient and versatile

These sounder/beacons can be put into different operating modes depending on local requirements. It provides high sound output at a low current, thus reducing power standby requirements and overall system cost. They are supplied with high/low volume settings as standard, allowing final audio adjustments to be made during installation.

The sounder is tone selectable during installation. 32 tone settings are available.

Safety & Security

Automatic daily self testing ensures that when the device is activated, everything works as expected. Pre-activation self testing ensures that a warning is raised before an event takes place, minimising the risk when notification is required. With the integrated isolator, continuity of operation is ensured even with a single short circuit on the loop.

Details

  • Standard first fix base shared with point detectors for ease of planning, logistics and installation
  • Integrated short circuit loop isolation for added safety protection
  • Base lock, address tag, trim skirt and surface cabling support for easy installation in all conditions
  • Loop powered with battery assisted activation allowing up to 128 devices per loop
  • 32 selectable tones at 4 selectable volume levels that can be reconfigured from the CIE
  • Integrated high-bright visual indication for drawing attention in noisy areas
  • Multi-stage evacuation support for application flexibility
  • Pre-and post activation self testing ensuring maximum safety
  • Automatic synchronisation
  • Tri-colour diagnostic LED indicator for fast commissioning and fault finding support

Technical specifications

General
Compatibility
Kidde Commercial Excellence Systems
Addressing method
DIL switch
Monitoring
Activated
Battery level
Continuously self-checking
Fault
Open circuit
Short circuit
Electrical
Power supply type
Batteries
Loop powered
Batteries
3 x CR123 (optional)
Operating voltage
17 to 29 VDC
Communication voltage
4 to 11 V pulsed
Current consumption
250 µA (Quiescent)
1.4 mA (Activated - from the loop with batteries installed)
Refer to installation sheet for consumption values when only loop powered
Sounder
Output level
55 to 102 dB(A) - Tone dependent
Output level adjustment
4 levels
Frequency
User selectable
Selectable tones
32
Synchronization
Supported
No. of stages
3
VID
Colour
Red
Flash frequency
0.5 Hz (1 flash every 2 s)
Synchronization
Supported
Isolation
Type
Negative line break
Loop current
5 mA (isolated)
Series resistance
<0.08 Ω
Switch current
1.05 A (continuous) / 1.4 A (pulsed)
Leakage current
<1 mA
Isolation voltage
14 to 15.5 VDC
Reconnect voltage
14 to 15.5 VDC
Physical
Physical dimensions
111 x 128 mm (Ø x H)
Net weight
300 g
Colour
Traffic white (RAL9016)
Mounting type
Base mount
Mounting position
Ceiling
Wall
Material
PC / ABS
Environmental
Operating temperature
-10 to +55°C
Storage temperature
−25 to +75°C
Relative humidity
10 to 93% (noncondensing)
Environment
Indoor
IP rating
IP21C
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-3, EN54-17