9-30436
Input/Output expansion card for Micra 10, Micra 25 and Micra 100, and variants
- 5 Outputs (4 alarm levels + fault)
- 3 Inputs (programable)
- Compatible with Micra 10, Micra 25 and Micra 100
- Compatible with Senator 10, 25 and 100
- Compatible with LaserSense 10, 25 and 100
At a glance
Description
The Input/Ouput expansion card is designed to provide additional relay outputs and/or inputs when interfacing to other systems. The Input/Ouput expansion card plugs into the APIC interface slot in each detector and cannot be used in conjunction with an APIC Card.
The Input/Ouput expansion card provides detector inputs that may be programmed for Remote Day/Night Mode Changeover, Remote Reset or ClassiFire Override as well as power
supply fault monitoring. ClassiFire Override is a particularly useful feature that enables the normal detector sensitivity to be reduced by a preprogrammed percentage to avoid unwanted alarms from a predictable event such as theatre stage effects or open fires in heritage buildings.
The Input/Ouput expansion card provides detector outputs for the 4 alarm levels, and the fault output. The fault output is normally closed, and open in case of a fault.
The Input/Ouput expansion card provides detector inputs that may be programmed for Remote Day/Night Mode Changeover, Remote Reset or ClassiFire Override as well as power
supply fault monitoring. ClassiFire Override is a particularly useful feature that enables the normal detector sensitivity to be reduced by a preprogrammed percentage to avoid unwanted alarms from a predictable event such as theatre stage effects or open fires in heritage buildings.
The Input/Ouput expansion card provides detector outputs for the 4 alarm levels, and the fault output. The fault output is normally closed, and open in case of a fault.
Details
- 5 Outputs (4 alarm levels + fault)
- 3 Inputs (programable)
- Compatible with Micra 10, Micra 25 and Micra 100
- Compatible with Senator 10, 25 and 100
- Compatible with LaserSense 10, 25 and 100
Technical specifications
| Physical | ||
|---|---|---|
| Physical dimensions |
71 x 102 x 26 mm (W x H x D)
|
|
| Mounting type |
PCB mount
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-10 to +60°C
|
|
| Relative humidity |
0 to 90% noncondensing
|
|
| Environment |
Indoor
|
|
| Regulatory | ||
|---|---|---|
| Certification |
EN54-20
FM
UL
|
|
| Mechanical | ||
|---|---|---|
| Mounting | 4 screws (supplied with unit) | |
| Outputs | ||
|---|---|---|
| Relays | 4 (Pre-alarm, Alarm, Alarm2 & Aux Alarm) + 1(Fault) | |
| Rating | 1A @ 24V | |
Downloads
All downloadsDatasheet
Installation sheet