240365
Conventional manual call point, Abort
- Conventional technology for use in most extinguishing control systems
- LED indication for activation status indication
- Operating instructions by means of standardised EN54-11 type symbols
- Attractive design housing made of robust die-cast aluminium
- Designed for surface mount applications
Related products
At a glance
General
The 240365 is a white, double action manual call point used as electrical abort device in extinguishing systems
It is connected to the fire detection or extinguishing control panel via a conventional detector line. A red status LED optically indicates the activated condition of the device.
Construction
In comparison with plastic housings, the robust design housing made of die-cast aluminium proves advantages even after years of use thanks to its resistance to environmental impact and minimal colour fading in sunlight. Design details such as the self-closing lock cover protect the inside from dust or water penetration and facilitate easy installation and cabling. The door with the easily replaceable glass pane has an opening angle of more than 180°.
When the call point is activated, the door is mechanically prevented from closing.
Details
- Conventional technology for use in most extinguishing control systems
- LED indication for activation status indication
- Operating instructions by means of standardised EN54-11 type symbols
- Attractive design housing made of robust die-cast aluminium
- Designed for surface mount applications
- EN standard type B manual call point, dual action
- 100 Ohm series resistor fitted
Technical specifications
| General | ||
|---|---|---|
| Status indication |
LED
|
|
| Compatibility |
Conventional detection & alarm systems
|
|
| Connectivity |
2-wire zone
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Zone powered
|
|
| Operating voltage |
10 to 30 VDC
|
|
| Cable specification |
<1.5 mm²
|
|
| Terminals |
6
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Manual activation
|
|
| Monitoring |
Off
On
|
|
| Installation height |
Determined by local regulation
|
|
| Output | ||
|---|---|---|
| Output quantity |
1
|
|
| Output type and rating |
Contact (25 VAC @ 2 A or 60 VDC @ 2 A)
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
127 x 127 x 35 mm (W x H x D)
|
|
| Net weight |
± 420 g
|
|
| Colour |
White (RAL 1013)
|
|
| Mounting type |
Surface mount
Wall mount
|
|
| Cable entries |
Top & bottom ( 2 x M20×1.5), Rear wall (2 x 24×10 mm)
|
|
| Material (body) |
Die-cast aluminium
|
|
| Functional marking |
ABORT
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-25 to +70°C (max. 12 h) (maximum application)
-20 to +60°C (continuous operation) (typical application)
|
|
| Relative humidity |
5 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP43 (standard)
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 3
WEEE
|
|
Downloads
All downloadsDatasheet
Installation sheet
Certificates
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.