Skip to main content

9-30436

Input/Output expansion card for Micra 10, Micra 25 and Micra 100, and variants
  • 5 Outputs (4 alarm levels + fault)
  • 3 Inputs (programable)
  • Compatible with Micra 10, Micra 25 and Micra 100
  • Compatible with Senator 10, 25 and 100
  • Compatible with LaserSense 10, 25 and 100
View all

At a glance

Description

The Input/Ouput expansion card is designed to provide additional relay outputs and/or inputs when interfacing to other systems. The Input/Ouput expansion card plugs into the APIC interface slot in each detector and cannot be used in conjunction with an APIC Card.

The Input/Ouput expansion card provides detector inputs that may be programmed for Remote Day/Night Mode Changeover, Remote Reset or ClassiFire Override as well as power
supply fault monitoring. ClassiFire Override is a particularly useful feature that enables the normal detector sensitivity to be reduced by a preprogrammed percentage to avoid unwanted alarms from a predictable event such as theatre stage effects or open fires in heritage buildings.

The Input/Ouput expansion card provides detector outputs for the 4 alarm levels, and the fault output. The fault output is normally closed, and open in case of a fault.

Details

  • 5 Outputs (4 alarm levels + fault)
  • 3 Inputs (programable)
  • Compatible with Micra 10, Micra 25 and Micra 100
  • Compatible with Senator 10, 25 and 100
  • Compatible with LaserSense 10, 25 and 100

Technical specifications

Physical
Physical dimensions
71 x 102 x 26 mm (W x H x D)
Mounting type
PCB mount
Environmental
Operating temperature
-10 to +60°C
Relative humidity
0 to 90% noncondensing
Environment
Indoor
Regulatory
Certification
EN54-20
FM
UL
Mechanical
Mounting 4 screws (supplied with unit)
Outputs
Relays 4 (Pre-alarm, Alarm, Alarm2 & Aux Alarm) + 1(Fault)
Rating 1A @ 24V

Downloads

All downloads

Datasheet

Installation sheet