NC-DBO

Conventional reflective beam detector
  • Wide operating voltage range
  • Large protection area
  • Combination of transmitter & receiver in one housing allows for easy installation and optical alignment
  • Intelligent microprocessor based decision making on fire and fault statuses
  • Easy alignment and commissioning with onboard laser and signal level indication
Visualizza tutto

A prima vista

General

The DC-9105E is a reflective infrared beam smoke detector for use in conventional fire detection systems. Being microprocessor based, the detector offers extensive algorithms for analysis and decision making. Taking ambient operating conditions into consideration, system adjustments such as drift compensation and alarm and fault analysis are automatic. The sensitivity of the detector is adjustable to suit various application conditions.

Operating mode

When connected to a compatible conventional fire alarm system, fire and fault information is reported via potential free relay contacts that can be easily interfaced into the system.

Installation

The number of reflectors in a system varies depending on the required operating distance (detection range) of the detector. Optical reflectors from 1 to 4 provide an effective range of the detector between 5 and 100 m. Four reflectors are supplied with the beam. The detection range of the beam can be selected from 4 levels with the standard GST hand held programmer (P-9910B). For very short range detection (>10 m), a non reflective mask (NRM9105) is recommended to attenuate the reflector.

Applications

The DC-9105E is particularly suitable for use in historical buildings, warehouses, large storage areas, shopping malls, leisure centres, exhibition halls, hotel lobbies, printing houses, clothing factories, museums and prisons.

Dettagli

  • Wide operating voltage range
  • Large protection area
  • Combination of transmitter & receiver in one housing allows for easy installation and optical alignment
  • Intelligent microprocessor based decision making on fire and fault statuses
  • Easy alignment and commissioning with onboard laser and signal level indication
  • Self-diagnostics for monitoring & reporting internal failures
  • Automatic drift compensation compensates for changing environmental conditions, dust and dirt accumulation, building movement and changing internal component specifications due to ageing
  • Onboard N/O fire and N/C fault dry contact outputs for easy supervision
  • Four selectable sensitivity levels for wide application coverage

Specifiche tecniche

General
Status indication
LEDs
Compatibility
All fire alarm systems with input supervision
Alarm levels
4
Connectivity
Relay contacts
Electrical
Power supply type
24 VDC
Operating voltage
18 to 28 VDC (24 VDC nominal)
Current consumption
≤20 mA (Commissioning)
≤12 mA (Standby)
≤22 mA (Alarm)
Cable specification
>1.5 mm² for DC power, >1.0 mm² twisted for others
No. of cable cores
2
Terminals
6
Detection
Detection principle
Optical light scatter
Monitoring
Alarm threshold
Fault
Sensitivity
1.3 to 2.8 dB, (26 to 48% OBS) selectable
Coverage area
<1400 m²
Zone length
<100 m
Range
5 to 100 m
Lateral detection
14 m
Adjustment angle
-6 to +6°
Misalignment tolerance
±0.5°
Output
Output quantity
2
Output type and rating
Alarm, Fault (2A @ 28 VD)
Physical
Physical dimensions
95 x 206 x 95 mm (W x H x D)
Shipping weight
450 g
Colour
Grey
Mounting type
Wall mount
Cable entries
2
Material (body)
ABS
Environmental
Vandal proof
No
Operating temperature
-10 to +50°C
Storage temperature
-20 to +60°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP20
IP66 with silicone seal
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Voluntary marks
BOSEC
Standards
EN54-12