EVERON-1700-STEP-UP
Always On. Always Aware.
EVERON-1700-STEP-UP
EVERON-1700-STEP-UP
- Everon 1700-MBC and ATSX700-RETRO, in ONE kit.
- Everon 1700-MBC
- MBC mounting plate
- Power Supply Unit (PSU)
- PSU mounting bracket
Alternative products
Related products
At a glance
Product overview
Everon upgrade kit
This kit contains the components needed to change the panel from Master to Everon or from Advisor Advance to Everon.
The kit contains the panel-MBC and MBC mounting plate, Power Supply Unit (PSU), PSU mounting bracket, Cables/NTC/Stand-offs and User manual. There are no Keypads or housings, etc included in this kit.
The kit contains the panel-MBC and MBC mounting plate, Power Supply Unit (PSU), PSU mounting bracket, Cables/NTC/Stand-offs and User manual. There are no Keypads or housings, etc included in this kit.
Details
- Everon 1700-MBC and ATSX700-RETRO, in ONE kit.
- Everon 1700-MBC
- MBC mounting plate
- Power Supply Unit (PSU)
- PSU mounting bracket
- Cables, NTC sensor, stand-offs and user manual
Technical specifications
| System | ||
|---|---|---|
| Product line |
Everon
|
|
| Product type |
Integrated Access Control
|
|
| Panel type |
Hybrid
|
|
| Kit |
No
|
|
| No. of keypads / readers |
8
|
|
| Data Gathering Panels (DGP) |
7
|
|
| No. of alarm groups |
256
|
|
| Specified cable |
WCAT52 / WCAT54 or equivalent
|
|
| Inputs | ||
|---|---|---|
| Max no. of inputs |
48
|
|
| Onboard inputs |
8
|
|
| Inputs plug-in expansion |
8
|
|
| ATS1202 support |
3
|
|
| Outputs | ||
|---|---|---|
| No. of outputs |
128
|
|
| No. of onboard outputs |
3 electronic outputs + 1 relay
|
|
| Area | ||
|---|---|---|
| No. of areas |
4
|
|
| User/Cards | ||
|---|---|---|
| Max. no. of users |
more than 2000
|
|
| Users with name |
1000
|
|
| Max. no. of cards |
2000 to 65532
|
|
| Max. no. of PIN codes |
2000 to 65532
|
|
| Access control | ||
|---|---|---|
| Standard doors on control panel |
4
|
|
| Door groups |
128
|
|
| Floor groups |
128
|
|
| Intelligent doors on 4-door DGPs |
28
|
|
| Communication | ||
|---|---|---|
| Onboard transmission type |
IP
|
|
| Transmission extension |
GSM
GSM/GPRS
GSM/GPRS/IP
IP
|
|
| Databus type |
RS485
|
|
| Event log | ||
|---|---|---|
| Alarm event log |
14500
|
|
| Access event log |
10000
|
|
| Electrical | ||
|---|---|---|
| Operating voltage |
24 VDC
|
|
| Mainboard current consumption |
110 mA at 24 V (PSU), 160 mA at 12 V (battery)
|
|
| Max system current |
950 mA at 13.8 V ±0.2 V
|
|
| Max aux power current |
2500 mA at 13.8 VDC ±0.4 V
|
|
| Auto-reset fuses |
3 (electrical, 1.3A per use)
|
|
| Glass break fuses |
1 (mains power, T-2A 230 VAC, slow)
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
199 x 140 x 45 mm
|
|
| Net weight |
435 g
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-10 to +55°C
|
|
| Relative humidity |
95% noncondensing
|
|
| Environmental Class |
Class II, indoor
|
|
| IP rating |
IP31
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
|
|
| Certification |
CE
|
|
| Supported versions | ||
|---|---|---|
| Version MR3.2 and above supports up to 48 zones; versions prior to MR3.2 supports up to 32 zones | ||
Downloads
All downloadsDatasheet
Technical documentation
User documentation
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.