Skip to main content

IU2055NC

Aritech 2000 Series conventional zone monitor unit
  • Monitors up to 30 standard conventional or up to 20 intrinsically safe conventional detectors
  • Zone supervised for open and short circuits
  • Supports alarm verification and CleanMe™ functions
  • Loop powered
  • Easy numeric addressing
View all

At a glance

Product overview

The IU2055NC is and addressable, 2000 Series two-wire zone monitor designed to provide an interface between conventional fire detectors and an addressable 2000 series protocol fire alarm control panel. The IU2055NC enables the addressable panel to monitor the presence and operation of up to 30 conventional detectors in standard or up to 20 in intrinsically safe configurations.

Application

The IU2055NC allows for the upgrade and inclusion of an existing or new conventional fire zone into and addressable detection loop. It supervises the conventional zone circuit for open and short circuits and monitors it for alarm conditions. Any abnormal conditions are reported to the control panel and are indicated on the IU2055NC with a yellow LED. The unit supports alarm verification and CleanMe™. It resets by cycling power to the zone circuit as directed by the fire panel.

Operation

The IU2055NC is connected to the panel via a two wire communication loop that provides power and carries control and input data. The module address is easily set with two rotary switches. The address setting is non-volatile and will not be lost in the event of a power failure.

The 2000 series conventional zone monitor utilizes an advanced digital data communications protocol that ensures the integrity of the data communication with extensive error correction algorithms.

Details

  • Monitors up to 30 standard conventional or up to 20 intrinsically safe conventional detectors
  • Zone supervised for open and short circuits
  • Supports alarm verification and CleanMe™ functions
  • Loop powered
  • Easy numeric addressing
  • Supports standard and intrinsically safe applications
  • CE/CPR certified to EN54:18

Technical specifications

General
Status indication
Alarm LED, Fault LED
Compatibility
Aritech 2000 Series systems
Addressing method
Rotary switch
Address range
1 to 128
Electrical
Power supply type
Loop powered
Operating voltage
21 to 28 VDC (loop)
17.5 to 18.5 VDC (zone)
Current consumption
<15 mA (standby)
<40 mA (alarm)
<3.6 mA (remote indicator)
Input
Input quantity
1
Input type and rating
Supervised, 19.4 mA max.
Input states
Active
Normal
Open
Short
Supervisory voltage
17.5 to 18.5 VDC
Termination resistor
3.9 kΩ, ¼ W, 5%
Zone resistance - normal mode <40 Ohm
Zone resistance - intrinsic safe mode <26 Ohm
Output
Output quantity
1 (remote indicator)
Output type and rating
Unsupervised, 3.6 mA
Physical
Physical dimensions
175 x 124 x 51 mm
Net weight
325 g
Colour
White
Mounting type
Wall mount
Cable entries
1
Material
Plastic
Cable specification
J-Y(ST)Y 2x2x0,8 rt, EB CY (TP) 2x2x0,75, KAL21A, KAL21B, KAL51A, KAL51B, KAL61A
Environmental
Vandal proof
No
Operating temperature
−10 to +55°C
Storage temperature
−20 to +60ºC
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IS
IP rating
IP40
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-18