KFP-CF2
Conventional Fire Panel - 2 Zone
- Modern, elegant design
- Easy removable parts for quick and clean installation
- Default regional setup modes
- Supervised alarm notification outputs
- EN54 compliant potential free fire & fault relays
Alternative products
At a glance
Overview
KFP-C fire control panels offer state of the art architecture in configurations that deliver an uncomplicated solution for small to mid-sized conventional applications. They feature an attractive contemporary design that fits with any decor. The gently curved door front offers a distinctive flair. Operator controls are inset in a striking grey lexan.
With a comprehensive line of conventional devices and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.
With a comprehensive line of conventional devices and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.
The Panel
The KFP-CF2 is a conventional fire alarm control panel. It is supplied in local language with 2 zones that support up to 20 devices per zone, as well as up to 2 supervised relay outputs dedicated to sounder control. In addition 2 conventional relay outputs dedicated to common fire and fault conditions, as well as two user configurable inputs for monitoring and control are available.
Options
The panels support 2 types of auxiliary relay boards, one with 4 standard relays, and one with 4 supervised relays. With these boards the panel outputs may be expanded with up to 8 additional outputs.
Approvals & Compliance
The product line carries the following accreditations:
• EN54:2, EN54:4 and CE approved
• CPD certified
• NEN2535, NBNS21-100 and BS5839-1 compliant
• WEEE compliant
• RoHS compliant
Type class conditions: 3K5 of IEC 60721-3-3
• EN54:2, EN54:4 and CE approved
• CPD certified
• NEN2535, NBNS21-100 and BS5839-1 compliant
• WEEE compliant
• RoHS compliant
Type class conditions: 3K5 of IEC 60721-3-3
Details
- Modern, elegant design
- Easy removable parts for quick and clean installation
- Default regional setup modes
- Supervised alarm notification outputs
- EN54 compliant potential free fire & fault relays
- Remote sounder control, day/night & reset facilities
- Auxiliary 24VDC supply output with reset support
- Default support for special functions such as: - EN54 compliant user access levels - mixed zones - full front panel diagnostics - one-man walk test
- Auxiliary standard & supervised relay output boards
- Networkable up to 64 zones
Technical specifications
| General | ||
|---|---|---|
| Maximum system capacity (device count) |
up to 2048
|
|
| Network size (nodes) |
up to 32
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
VAC
|
|
| Power consumption |
2 A @ 24 VDC
|
|
| Operating voltage |
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Cable type: 3 x 1.5 mm² (live, neutral, earth)
|
|
| Current consumption |
2 A @ 110/240 VAC
130 mA (Alarm current (no devices)
50 mA (Quiescent current (no devices)
|
|
| Loop | ||
|---|---|---|
| Maximum loop capacity |
2
|
|
| Zone | ||
|---|---|---|
| Maximum zone capacity |
up to 2
|
|
| Operating voltage |
22 VDC (18 to 24 VDC)
|
|
| Quantity of devices per zone |
20 max.
|
|
| Rating |
65 mA (max. Load)
|
|
| Cable rating |
40 ohm (max. resistance), 500 nfF (max. capacitance)
|
|
| Input | ||
|---|---|---|
| Input quantity |
2
|
|
| Input type and rating |
100 ohm (max. cable resistance)
|
|
| Standby battery | ||
|---|---|---|
| Capacity |
2 x 12 V, 7.2 Ah (SLA)
|
|
| Physical | ||
|---|---|---|
| Form factor |
Small
|
|
| Physical dimensions |
435 x 129 x 320 mm (W x H x D)
|
|
| Net weight |
2.8 kg (without battery)
|
|
| Shipping weight |
4.5 kg
|
|
| Colour |
Pure white (RAL 9010)
|
|
| Mounting type |
Surface mount
|
|
| Cable entries |
Ø 20 mm - 14 / 2 / 12 (Top / Bottom / Rear)
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-5 to +50°C
|
|
| Storage temperature |
-20 to +70°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP30
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CPD
RoHS
WEEE
|
|
| Certification |
EN54-13
EN54-2
EN54-4
|
|
| Supervised Outputs | ||
|---|---|---|
| 2 | ||
| Output voltage | -15 to +28 VDC | |
| Load (max.) | 250 mA | |
| Non Supervised Outputs | ||
|---|---|---|
| 2 | ||
| Load | 2 A @ 30 VDC | |
| Auxilliary Supply Output | ||
|---|---|---|
| Output voltage | 24 VDC (21 to 28 VDC) | |
| Load (max.) | 250 mA | |
Downloads
All downloadsDatasheet
Technical documentation
Quick operation guide
Other technical documentation
Certificates
CPD / CPR
Compatibility list
Other EU certificate
Other EU certificate
VMC_B-9212-FD-K876-e_KFP-CF2
Other EU certificate
VMC_B-9212-FD-916-c_KFP-CF2 series
Other EU certificate
VMC_232.252_1X series
Other EU certificate
VMC_1199b-(cl-1)_1X-F, KFP-CF, ZP1-F
Other EU certificate
VMC_PR-1938/064_Kilsen KFP GST series
Other EU certificate
VMC_PR-1723/064_KFP-A
User documentation
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.