The IU2080NC utilizes an advanced digital data communications protocol that ensures the integrity of the data communication with extensive error correction algorithms. It ensures system reliability with continuous supervision and monitoring of the output circuit for open or short circuit conditions, as well as monitoring of the input auxiliary power supply for low voltage or fault conditions. The output circuit supports a continuous or pulsing output that significantly simplifies meeting requirements for differentiation of audible alarms for different alarm circumstances.

Installation

The IU2080NC loop address is set with a simple decimal rotary dial and is non-volatile - the address is not lost in the event of a power outage. The module is simply connected to a compatible fire alarm panel via a two-wire device communication loop that carries both data and operating power to the module. The indicating circuit is powered via a auxiliary power supply.

Programmability

The operation of the IU2080NC is fully configurable from the CIE (control panel) allowing for powerful and extremely flexible output configuration capabilities.

Specifiche tecniche

General
Addressing method
Rotary switch
Electrical
Power supply type
24 VDC
Alimentato ad anello
Physical
Colour
Hvid
Mounting type
Montaggio a superficie
Material
Plastic
Environmental
Vandal proof
No
Environment
Indendør
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR